On a controlled office door the card reader gets the attention, but two small sensors beside it decide whether the system tells the truth: the door position switch that knows if the door is actually shut, and the request-to-exit sensor that knows someone is leaving from the inside. Across the medical suites, office condos and storefront spaces of Cinco Ranch, Grand Lakes and the Grand Parkway corridor, most nuisance alarms trace back to how those two parts were chosen, aimed and wired.
Which sensors a controlled office door actually needs
A card reader decides who may open a door. The sensors decide what the access system believes happened afterward, and when they are wrong the event log fills with alarms nobody trusts.
Three inputs matter on a typical controlled office door:
- Door position switch (DPS). A magnetic reed contact in the frame paired with a magnet in the door. When the door closes, the magnet holds the contact in its normal state and the controller reads the opening as secure. Without one, the system cannot tell a forced entry from a normal one, and it cannot warn that somebody propped the door.
- Request-to-exit (REX). Either a passive infrared motion detector above the door on the secure side, or a switch built into the inside lever. It tells the controller that the opening it is about to see is someone leaving, so the door-forced alarm is suppressed and, on magnetic-lock doors, power to the lock is cut.
- Lock monitoring. Some electrified locks and electric strikes report latch or bolt status. It is optional, but it is the only way to know that a door which looks closed actually latched.
| Sensor | What it reports | Typical symptom when it is wrong |
|---|---|---|
| Door position switch | Door open or closed | False door-forced alarms, or silence when a door is propped |
| Motion REX | A person approaching to leave | Door releases when someone walks past inside |
| Lever REX switch | Inside handle turned | Forced alarms when people push the door without touching the lever |
| Latch or bolt monitor | Lock actually engaged | Door shows secure while the latch rests on the lip of the strike |
Occupancy and people-counting sensors are a separate category; mention it when you call if that is what you mean.
What the doors in 77494 office space are made of
Sensor choice starts with the door and frame. Cinco Ranch, Grand Lakes, Seven Meadows and the Grand Parkway and Westpark Tollway corridors hold many newer professional buildings, while retail-office strips near Katy Mills and the Interstate 10 frontage lean toward storefront glass.
Aluminum storefront entries
Strip-center suites have narrow-stile doors under a hollow header. A recessed contact often fits that header; when the extrusion shape rules it out, a low-profile surface contact does the job. The glass matters more for the REX, because a motion detector that can see through the door also sees the sidewalk.
Hollow metal frames in medical and professional condos
Newer office condos and medical suites typically pair steel frames with solid-core doors. A contact recessed into the frame head looks clean and is hard to tamper with, but steel changes how close the magnet must sit, so the part has to be rated for steel mounting. Frames are sometimes filled with grout, which changes the drilling plan. If the opening carries a fire label, field modification is limited, and we confirm the rating before drilling anything.
Flex and warehouse-office buildings
Tilt-wall buildings with a front office and a warehouse behind need sensors on steel man doors and often on roll-up overhead doors. Overhead doors get heavy-duty floor-mounted contacts with armored cable, because a standard frame contact would not survive a pallet jack or a door that shifts in its track.
All-glass suite fronts with no frame at all need contacts made for glass doors or lock hardware that reports its own status.
Aiming a request-to-exit sensor so it only sees people leaving
A motion REX is mounted on the secure side, normally on the wall or ceiling just above the door, with its pattern angled down toward the spot where someone stands to open it. The goal is a narrow zone at the threshold, not a view of the room. Most units have an adjustable lens or a strip that can be masked so the detector ignores everything beyond that zone.
False triggers in office suites usually come from a short list:
- a supply air diffuser blowing across the lens, which a PIR can read as movement as warm and cool air shift;
- afternoon sun through a west-facing storefront heating the floor tile inside the detector’s view;
- staff walking along a glass sidelight or a hallway the pattern was never masked from;
- a unit mounted so high or so far back that its pattern reaches the reception desk.
The REX hold time should cover one person walking through and, on maglock doors, no more, since every extra second leaves the door unlocked. Where the inside has a mechanical lever, a switch in the lever trim is more precise because it fires only when the handle turns; it needs electrified trim or a retrofit kit, wired to the frame through an electric hinge or door loop.
Magnetic locks and the extra exit hardware they bring
A maglock has no handle that releases it. Everyone inside depends on the electronics to let them out, so these doors carry more requirements than an electric strike does. Under the sensor-release provisions of the International Building Code, which Texas jurisdictions commonly adopt, the usual expectations are:
- a sensor on the egress side that unlocks the door as someone approaches, and that unlocks it if the sensor itself loses power;
- a manual button marked PUSH TO EXIT, mounted 40 to 48 inches above the floor and within 5 feet of the door, that cuts lock power directly rather than asking the access controller, and keeps the door unlocked for at least 30 seconds;
- release on fire alarm activation where the building has a fire alarm or sprinkler system;
- a lock that releases whenever its power is lost.
Because 77494 crosses the Katy city limits and the Harris and Fort Bend county line, which fire marshal interprets these rules depends on the address, and we design to what that office accepts. Where a door already has a usable lever, an electric strike or electrified lever is usually the better choice, since nobody leaving depends on a sensor.
Cable, supervision and the controller settings behind each door
A composite access-control cable bundles reader, lock power, door contact and REX conductors in one jacket, giving one tidy home run per opening with no splices hidden above the ceiling. Tenant-suite ceilings are very often return-air plenums, so that cable must be plenum-rated.
Supervision is the detail that separates a sensor that reports from one that can be trusted. Many controllers can read end-of-line resistors placed at the device, which lets the input distinguish closed, open, cut and shorted. With the resistors at the sensor, somebody who shorts the contact wires to defeat it produces a trouble alarm instead of a reassuring door-closed. Resistors parked at the panel end protect only the last inch of cable.
Controller settings are often left at default. We match input type to the contact, set door-held time to suit deliveries at a clinic’s back door, set REX shunt time, and turn on relock-on-close so a strike does not stay released after someone has already walked through.
Electric strikes and maglocks are coils, and when the controller switches one off it kicks back a voltage spike. A suppression device across the lock terminals, a diode on DC hardware, protects the relay contacts and keeps that spike from appearing as noise on nearby sensor inputs.
What happens when EVOTECH comes out for sensor work
- Walk every controlled door with whoever manages the suite, noting door, frame, hardware and what each opening protects.
- Identify the controller and check free inputs, current configuration and whether an expansion module is needed.
- On an existing system, pull the event log and match alarms to doors; the pattern of false events usually points straight at the faulty sensor.
- Send an itemized quote by door, with maglock life-safety items listed separately.
- Install, terminate with supervision where supported, and configure each input.
- Walk-test every door: valid card, forced, held, REX coverage checked from the hallway side, and fire alarm release and power loss on maglock doors.
- Label each input to its door and leave a short sheet explaining every alarm.
EVOTECH IT LLC is a licensed and insured low-voltage contractor with more than twenty years of work around Katy, and landlords commonly ask for exactly that paperwork before anyone goes above their ceiling.
What moves the price, and the mistakes that bring a technician back
Price follows the door count and how hard each door is: recessed contacts in steel or grout-filled frames, fire-rated openings, hard drywall ceilings, long runs to the controller, an expansion board when inputs run out, lever-integrated REX trim with electric hinges, maglock egress hardware, and after-hours scheduling. Each appears as its own line, so you can see what every door adds.
- Gap drift. A heavy door sags on its hinges over a few months, the magnet moves away from the contact and the door starts reporting open at random. Checking the gap with the door pushed and pulled, and tightening hinges first, prevents it.
- Wrong contact for steel. A standard contact on a steel frame may pass on install day and then fail once the door settles.
- Door-held time that fights the staff. If the buzzer sounds with every delivery, someone props the door and silences it, and the sensor might as well not exist.
- Unlabeled inputs. Six months later nobody remembers that input three is the back door.
Related services
Frequently asked questions
Why does our system log door forced open when nobody forced the door?
Can you add sensors to a system another company installed?
Our door has an ordinary lever on the inside. Does it still need a REX?
Can a motion REX be set so it does not unlock the door?
Can the work happen while our clinic is closed?
Book an on-site estimate for your Katy office doors
We walk each controlled door, read your event log, and send an itemized, door-by-door quote that shows exactly which sensors and settings each opening needs. Call (832) 359-2425.
Book an on-site estimate