Roll-up doors, dock doors and hollow metal man doors monitored properly: armored leads, impact-tolerant housings, per-door reporting, and a clean hand-off into the panel, access controller or building system you already run.
A man door and a 14-foot roll-up are not the same job
Facilities managers ask for door monitoring as one line item, and it is almost always two or three different scopes wearing one name. What separates them is how far the door travels, how much it wanders while travelling, and what happens in the space around the hardware all day.
Hollow metal man doors
The straightforward part of the scope. A personnel door moves in a tight arc on hinges, its frame is fixed, and separation between the two halves at rest is small and predictable. The only real complications are that the frame is steel – which shortens the usable separation distance of any contact screwed to it – and that grouted frames cannot be fished, so the wire path has to be planned rather than assumed.
Sectional and roll-up doors
These are a different animal. A sectional door rides in tracks with deliberate clearance, so it does not return to exactly the same place twice; a rolling steel curtain can drift further still. Hardware for these is specified with separation tolerance measured in inches rather than fractions, because a part chosen for a swing door will report open every time the curtain settles half an inch off centre.
Dock doors specifically
A dock position adds traffic. Pallet jacks, forklift forks, hand trucks and water all pass across the threshold, repeatedly, every working day. Hardware survives there because of where it is placed and what it is wrapped in, not because of the switch inside it.
Counting matters too. Six dock positions wired onto one panel zone will tell you that a dock door is open. It will not tell you which one, which is the only fact anybody needs at eleven at night.
Housings, armored leads, and where a switch survives a pallet jack
The standard approach on an overhead door is a steel-housed contact set into the floor near the door line, with its magnet on an angle bracket bolted to the bottom section of the door. It works, and it is directly in the path of everything that moves through the opening.
Where the traffic is heavy we prefer to get the hardware out of the floor entirely: mount the switch on the jamb or guide at mid-height and carry the magnet on a bracket fixed to the end of the curtain or to the door’s side track. Same reported state, nothing to run over, nothing sitting in wash-down water. Where a floor position genuinely is the only option, it goes in a recessed steel box set flush, not proud of the slab.
What to specify
- Armored flexible lead. A stainless armor jacket from the contact body back to a junction box resists abrasion, impact and rodents. Plain jacketed cable at a dock door is a scheduled failure.
- Separation tolerance with margin. Overhead hardware is rated in inches for a reason; we still leave headroom beyond the measured travel rather than specifying to the number we found on a calm Tuesday.
- Sealed housings where there is moisture. Wash-down bays, exterior openings and refrigerated spaces all need a rated enclosure and a proper cable entry.
- Temperature rating for cold rooms. Coolers and freezers cycle through dew point, so condensation and frost inside an unsealed housing are a matter of time.
- Tamper where it matters. On controlled-stock areas, a housing that reports being removed from the frame covers an attack a plain contact cannot see.
One constraint overrides all of the above. A labeled fire door or fire-rated frame cannot be drilled or modified without voiding its listing, and that includes the tidy field bore somebody suggests to hide a wire. On rated openings we use surface hardware or a listed assembly designed for the purpose.
Cable, conduit, and keeping the run out of harm’s way
In a warehouse or flex building the cable is usually more exposed than the sensor, and it is what we spend the planning on. Runs that cross open ceiling space, drop down a wall in a forklift aisle, or leave a conditioned area for a dock canopy all need physical protection appropriate to where they are, and the local authority having jurisdiction has the final word on how that is done in your building.
- Protect the vulnerable sections, not just the whole run on principle. Conduit or raceway from floor level up to a safe height in traffic areas, then supported cable above.
- Junction properly. The armored lead off a contact is short by design; it terminates in an accessible box, not in a wirenut taped inside a track.
- Leave slack where things move. A service loop at the door end means the next person can drop the contact out for inspection without re-pulling the run.
- Respect the environment rating of the space the cable passes through, including any air-handling plenum.
- Separate from line voltage. Parallel runs alongside power invite induced noise on a long signal pair; crossings at right angles do not.
- Home-run the doors that matter. A point per door costs a little more cable and buys reporting that names the opening.
Everything on a dock is a high-cycle environment. Reed switches themselves tolerate very large numbers of operations, so when a monitored dock position fails it is nearly always the mounting bracket, the bolt that worked loose, or the cable flexing at a fixed point – which is why we fix the moving-side bracket properly and never let a conductor take the movement.
Feeding the contact into whatever already runs the building
A door contact is a dry contact: a pair of terminals that open or close, carrying no voltage of its own. That makes it easy to hand to almost any system, provided two things are respected.
Get the contact form right
Most alarm contacts are a simple normally-closed pair, which suits an intrusion panel. Building automation controllers and PLC inputs sometimes want the opposite sense, and specifications frequently call for a changeover arrangement providing both a normally-open and a normally-closed connection from one device. Asking that question before the parts are ordered avoids a cabinet full of relays added later to invert signals that could have arrived the right way round.
Do not switch load through the sensor
This is the mistake that damages equipment. A magnetic reed is a signal-level device with a modest current rating, and inductive loads are harder on it than the raw number suggests. It should never directly drive a strike, a motor starter, a horn or a contactor coil. Where a door state needs to operate something, the contact drives an interposing relay and the relay drives the load – which also isolates your sensing circuit from whatever that load does when it fails.
Where the logic actually lives
The sensor reports position and nothing more. Held-open timers, forced-open logic, shift schedules, escalation and notification all live in the panel, access controller, building system or PLC program that receives the signal. When somebody asks for a fifteen-minute open alert, the contact is the input; the timer is a configuration task on the receiving system, and we will tell you which side of that line your request falls on before quoting it.
How EVOTECH runs a commercial door-monitoring install
Worth knowing about this ZIP: 77492 is a Katy box-mail range, not a street delivery zone, so companies billing to a 77492 address operate from a site somewhere else in the area – flex and warehouse space off the I-10 frontage, light industrial pockets along Clay Road and out toward the Grand Parkway, or a suite in one of the newer retail and medical centres. Tell us where the doors physically are when you book, because the survey and the crew scheduling are built around that location.
- Site survey with the person who runs the doors. Usually a facilities lead or a warehouse supervisor rather than the office. They know which door gets propped, which one has been hit, and which one nobody uses.
- Document every opening. Type, size, operator, frame material, fire rating, traffic level and existing hardware – photographed, because the specification decisions come out of that record.
- Confirm the receiving system. Panel, access controller, building system or PLC; available inputs; the contact form it expects; whether point-per-door reporting is wanted where zones are short.
- Agree the work window. Dock work during receiving hours is disruptive and slower; most of our commercial installs in Katy run early, late or on a weekend by arrangement.
- Install and protect. Hardware placed out of the traffic path where possible, armored leads, protection on exposed cable, everything terminated in accessible boxes.
- Cycle test under real conditions. Each door operated repeatedly through its full travel, confirming the reported state changes cleanly and does not chatter as the curtain settles.
- Document and label. A drawing or list tying each physical door to its point name, so an alert at eleven at night sends somebody to the right end of the building.
What a Katy facility quote turns on
We survey at no charge and break the pricing out opening by opening, so a scope can be phased across budget years instead of taken all at once.
- Door count and door type. A run of identical man doors is efficient; a mix of sectional, rolling and personnel doors is several specifications in one visit.
- Where the hardware can be mounted. Jamb and track positions are usually quicker and more durable than cutting in a recessed floor box.
- Cable route and protection. Open joists over an aisle are fast; conduit runs and core drilling are not.
- Working height. Anything needing a lift rather than a ladder changes the day.
- Receiving system capacity. Spare inputs cost nothing; expansion modules, interposing relays and new terminations are parts and labour.
- Environment. Refrigerated, wash-down and exterior positions carry rated hardware and more careful sealing.
- Access and hours. After-hours work, escorted access and site induction requirements all take time before the first hole is drilled.
Related services
Frequently asked questions
Can you monitor a dock door without putting anything on the floor?
Our doors are fire-rated. Can you drill them?
We want an alert when a dock door has been open fifteen minutes. Is that the sensor or the panel?
Will contacts survive in a cooler or freezer?
Can the door contact feed our PLC or shut equipment down?